InTouch&PROFINET

In addition, I describe the InTouch connection to the Siemens controller via the Profinet protocol. The driver installation is similar to the configuration with Modbus TCP, but with a number of features

Conditions of the problem:
We have two computers, which is installed on the first Windows7 Professional 64, on the second Windows7 Maximum 64.
VMware Workstation 12 Pro virtual machines are installed on both computers
Where Wonderware software is installed – W7 PROFF 64
Where is TIA + Step7 installed – W7 PROFF x86

1. It is necessary to make so that virtual machines could see each other in the common network space of the home network (192.168.1.ххх)
1.1 Configuring the network adapters of virtual machines to the mode of auto-bridge
1.2 Confirm the invitation to the home network
1.3 We ping both machines to make sure the settings are correct
2. Configure the virtual machine where the Siemens software is installed
2.1 Running Nettoplcsim.exe
2.2 Launch Port 102 Capture
2.3 Running the Simatic Manager
2.4 Having opened our project, go to the Hardware Editor. We expose the IP address is the same as the virtual machine. In the project, a DB1 data block with one variable of type INT
2.5 Set PG / PC Interface set PLCSIM (TCP / IP)
2.6 We start the staff simulator and load the project into it
2.7 In the settings of the network loudspeaker NetToPLCsim we expose two identical addresses equal to the address of our virtual machine
2.8 Click on the start of the server
3. Configure InTouch
3.1 Install the driver for connection to Siemens controllers – DASSIDirect.3
3.2 Configure the driver as shown in the pictures below
3.3 Run the driver
3.4 Setting the Access Name
3.5 Creating a tag
3.6 Bind this tag to the animation symbol on the screen form
3.7 Run the project in Runtime mode

 

InTouch&PROFINET

Адреса Intouch

DASSIDIRECT

DASSIDIRECT

DASSIDIRECT

DASSIDIRECT

DASSIDIRECT

InTouchInTouch

InTouch