Expertune

... (secondary) circuit. If this requirement is not met, then it is necessary to reconfigure the outer loop so that its RRT is 3 times larger than that of the inner loop. In addition to RRT, the speed of contours can be estimated from the values ​​of the settings of I (TI). To configure the cascade, first configure the internal loop in local mode (with the cascade open). Then go into cascade mode and configure the outer loop. Procedure for testing and setting up cascading circuits: • Set the internal (secondary) circuit to the local LOCAL mode (the cascade is open, the SP job is entered manually). • Test the internal circuit and collect the PV and CO data, as described in the corresponding section of the ...